TOPFLEX®-EMV-UV-3-PLUS-2XSLCHK-J
Buy items
Technical Data TOPFLEX®-EMV-UV-3-PLUS-2XSLCHK-J
Motor connection cable for frequency converters in alignment with DIN VDE 0250 | |
Temperature range | flexible -15°C to +90°C fixed -40°C to +90°C |
Conductor operating temperature | +90°C |
Nominal voltage | AC U0/U 600/1000 V |
Max. permissible operating voltage | alternating current (AC) conductor/ground 700 V three-phase alternating current (AC) conductor/conductor 1200 V direct current (DC) conductor/ground 900 V direct current (DC) conductor/conductor 1800 V |
Test voltage conductor/conductor | 4000 V |
Coupling resistance | see datasheet |
Minimum bend radius | flexible <12 mm: 10x Outer ø 12-20 mm: 15x Outer ø >20 mm: 20x Outer ø fixed <12 mm: 5x Outer ø 12-20 mm: 7.5x Outer ø >20 mm: 10x Outer ø |
Details TOPFLEX®-EMV-UV-3-PLUS-2XSLCHK-J
Cable Structure
-
- Copper wire bare, finely stranded acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
-
- Conductor insulation: XLPE
-
- Conductor identification: brown, black, gray, green-yellow (divided into thirds)
-
- Ground conductor: GN-YE divided into thirds (3+3 conductor structure)
-
- Conductors stranded with optimal lay lengths
-
- 1. Shield: plastic-coated aluminum foil (St)
- 2. Shield: tinned copper braided shield, approx. coverage 85%
-
- Outer jacket: Special-Polyolefin
-
- Jacket color: black (RAL 9005)
-
- Length marking: in meters
Properties
-
- resistant to: UV radiation, weathering effects
-
- for outdoor use
-
- halogen-free
-
- optimal shielding enables interference-free operation of frequency converters
-
- low coupling resistance ensures good electromagnetic compatibility
-
- low mutual capacitance of the individual conductors due to XLPE conductor insulation and low shield capacity, enable low power transmission loss
Tests
-
- combustible gas corrosiveness acc. to DIN VDE 0482-754-2 / DIN EN 60754-2 / IEC 60754-2
-
- flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
-
- bundle fire test acc. to DIN VDE 0482-332-3-24 / DIN EN 60332-3-24 / IEC 60332-3-24
-
- smoke density acc. to DIN VDE 0482-1034-1+2 / DIN EN 61034-1+2 / IEC 61034-1+2
-
- UV-resistant acc. to DIN EN ISO 4892-2
-
- weather-resistant acc. to DIN EN ISO 4892-2
-
- electromagnetic compatibility acc. to DIN VDE 0875-11 / DIN EN 55011
Notes
-
- the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only
Application
-
- Used as a connecting cable for medium mechanical stress with fixed installation and occasional free movement in dry, damp or wet rooms, as well as outdoors. As a result of the permissible operating temperature of +90°C at the conductor, an enhanced current carrying capacity compared to PE insulated motor connection cables is permissible. Used in the automotive industry, food industry, environmental technology sector, packaging industry and in machine tools. Utilised as handling equipment for SIMOVERT drives in the industrial sector for pumps, fans, conveyor belts and air conditioning systems etc. EMC= Electromagnetic Compatibility; in order to optimise EMC properties, we recommend a double-sided and all-round large contact area of the copper braiding.
Items TOPFLEX®-EMV-UV-3-PLUS-2XSLCHK-J
Item description
Part no.
|
AWG (approx.) | Outer Ø mm (approx.) | Cu factor per km | Weight kg/km (approx.) |
---|