SY-JZ / SY-OZ
  • VDE Certification
  • EAC Certification
  • IPA Clean Room Certification
  • Length Marking In Meters
  • UKCA Certification
  • largely oil resistant
  • transparent outer jacket
  • with PVC inner jacket
  • galvanized steel wire braid to protect against mechanical damage
  • versatile use in many industries, particularly in machine building and plant engineering
Buy items

Technical Data

PVC control and connection cable in alignment with DIN VDE 0285-525-2-51 / DIN EN 50525-2-51
Temperature range flexible -15°C to +80°C
fixed -40°C to +80°C
Nominal voltage AC U0/U 300/500 V
Test voltage conductor/conductor 4000 V
Breakdown voltage 8000 V
Minimum bend radius flexible 20x Outer Ø
fixed 6x Outer Ø

Details

Cable Structure

      • Copper wire bare, finely stranded acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
      • Conductor insulation: PVC, compound type Z 7225
      • Conductor identification acc. to DIN VDE 0293-334, black conductors with consecutive white numbers
      • Ground conductor: starting with 3 conductors,
      • G = with GN-YE ground, in the outer layer,
      • x = without ground conductor (OZ)
      • Conductors stranded in layers with optimal lay lengths
      • Inner jacket: PVC
      • Steel wire braid, galvanized
      • Outer jacket: PVC
      • Jacket color: transparent
      • Length marking: in meters

Properties

      • largely resistant to: oil,
      • for details, see "Technical Information"

Tests

      • flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
      • certifications and approvals:
      • EAC
      • VDE Reg. No. 7032, valid for temperature range up to +70°C

Notes

      • the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only
      • cleanroom qualification tested on analog types; please note "cleanroom qualification" in your order

Application

      • Used as a connection and control cable for flexible applications involving medium mechanical stress with free movement, without tensile stress and without forced motion control in dry, damp and wet rooms, however, not suitable for outdoor use in machine tools, plant construction and data technology. Due to the dense braiding, the cable is well protected against mechanical damage. The galvanisation of the braid prevents corrosion and guarantees improved solderability of the braid.

Items SY-JZ / SY-OZ

No. of Conductors
Cross Section (mm²)
Protective Conductor (GN-YE)
Outer Diameter
Item description
Part no.
AWG (approx.) Outer Ø mm (approx.) Cu factor per km Weight kg/km (approx.)