PAAR-CY-OZ
  • EAC Certification
  • Length Marking In Meters
  • UKCA Certification
  • number coded
  • EMC-preferred type
Buy items

Technical Data

PVC data cable in alignment with DIN VDE 0812
Temperature range flexible -15°C to +80°C
fixed -40°C to +80°C
Nominal voltage AC U0/U 300/500 V
Test voltage conductor/conductor 1200 V
Test voltage conductor/shield 800 V
Breakdown voltage 2400 V
Mutual capacitance conductor/conductor at 800 Hz, approx. 150 pF/m
Mutual capacitance conductor/shield at 800 Hz, approx. 270 pF/m
Inductance approx. 0.67 mH/km
Coupling resistance at 30 MHz, approx. 250 Ohm/km
Minimum bend radius flexible 10x Outer Ø
fixed 5x Outer Ø

Details

Cable Structure

      • Copper wire bare, finely stranded acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
      • Conductor insulation: PVC acc. to DIN VDE 0207-363-3 / DIN EN 50363-3 (compound type TI2)
      • Conductor identification acc. to DIN VDE 0293-334, black conductors with consecutive white numbers
      • x = without ground conductor
      • Conductors stranded in pairs with optimal lay lengths, Pairs stranded in layers with optimal lay lengths
      • Foil wrap
      • Shield: tinned copper braided shield, approx. coverage 85%
      • Outer jacket: PVC acc. to DIN VDE 0207-363-4-1 / DIN EN 50363-4-1 (compound type TM2)
      • Jacket color: gray (RAL 7032)
      • Length marking: in meters

Properties

      • largely resistant to: oil,
      • for details, see "Technical Information"

Tests

      • flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
      • certifications and approvals:
      • EAC

Notes

      • the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only

Application

      • Suitable for flexible applications with free movement, without tensile stress and without forced motion control in dry, damp and wet rooms, however, not suitable for outdoor use. Used as a connection cable for signal, measurement and control technology, as well as in electronic engineering. Also applicable in pulse and data technology. Special areas of application include locations with high electromagnetic radiation, e.g. through adjacent lines. EMC= Electromagnetic Compatibility; in order to optimise EMC properties, we recommend a double-sided and all-round large contact area of the copper braiding.

Items PAAR-CY-OZ

No. of Conductors
No. of Pairs
Cross Section (mm²)
Outer Diameter
Item description
Part no.
AWG (approx.) Outer Ø mm (approx.) Cu factor per km Weight kg/km (approx.)

Accessories

Products That Match This Product

Info Circlechevron-leftAlertBrowse fileDownload fileFileImagePdfWordTextExcelPowerpointArchiveCsvAudioVideoSpinnerCalendarSort NoneSort ASCSort DESCReturn arrowMinusYouTubeSyncVisibleInvisible