DATAFLAMM®-C
- halogen-free
- color code DIN 47100
- with drain wire
- EMC-preferred type
- low capacity values due to PE-insulated conductors
Technical Data DATAFLAMM®-C
Data cable | |
Temperature range | flexible +5°C to +70°C fixed -40°C to +70°C |
Peak operating voltage | 0.14 mm²: 350 V 0.25 - 0.75 mm²: 500 V (not for high power current installation purposes) |
Test voltage conductor/conductor | 0.14 mm²: 800 V 0.25 - 0.75 mm²: 1200 V |
Mutual capacitance conductor/conductor | at 800 Hz, approx. 70 pF/m |
Coupling resistance | at 30 MHz, approx. 250 Ohm/km |
Minimum bend radius | flexible 7.5x Outer Ø fixed 4x Outer Ø |
Details DATAFLAMM®-C
Cable Structure
-
- Copper wire bare, 0.5 - 0.75 mm²: finely stranded acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
-
- Wire structure:
- 0.14 mm²: approx. 18 x 0.1 mm
- 0.25 mm²: approx. 14 x 0.15 mm
- 0.34 mm²: 7 x 0.25 mm
-
- Conductor insulation: PE acc. to DIN VDE 0819-103 / DIN EN 50290-2-23 (compound type LD/MD)
-
- Conductor identification acc. to DIN 47100, color coded
-
- x = without ground conductor
-
- Conductors stranded in layers with optimal lay lengths
-
- Foil wrap
-
- Drain wire, tinned copper
-
- Shield: tinned copper braided shield, approx. coverage 85%
-
- Foil wrap
-
- Outer jacket: thermoplastic compound acc. to DIN VDE 0207-24 (compound type HM2)
-
- Jacket color: gray (RAL 7005)
-
- Length marking: in meters
Properties
-
- halogen-free
-
- PE-insulated conductors ensure substantially lower capacity values than PVC-insulated conductors
Tests
-
- halogen-free acc. to DIN VDE 0482-754-1 / DIN EN 60754-1 / IEC 60754-1
-
- combustible gas corrosiveness acc. to DIN VDE 0482-754-2 / DIN EN 60754-2 / IEC 60754-2
-
- flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2 (outer jacket)
-
- certifications and approvals:
- EAC
Notes
-
- the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only
Application
-
- Used as a connection cable for signal, measurement and control technology, call systems and intercoms, clock systems, electronic weighing equipment and office machines. The cables can be laid on plaster and in dry, damp and wet rooms. Areas of application include telecommunication devices and information processing systems in public buildings, laboratories, department stores and other buildings where the release of halogens must be avoided in the event of fire. Interference-free screening ensures protection against external pulse generators or high-frequency signals. EMC= Electromagnetic Compatibility; in order to optimise EMC properties, we recommend a double-sided and all-round large contact area of the copper braiding.
Items DATAFLAMM®-C
Item description
Part no.
|
AWG (approx.) | Outer Ø mm (approx.) | Cu factor per km | Weight kg/km (approx.) |
---|