NA2XS(FL)2Y

  • VDE certification
  • direct burial

Technical Data

Medium voltage cable acc. to DIN VDE 0276-620, HD 620 S2, IEC 60502
Temperature range during installation -20°C
Permissible operating temperature of the conductor +90°C
Short circuit temperature at the conductor +250°C (Short circuit temperature max. 5 s)
Nominal voltage see datasheet
Operating voltage see datasheet
Test voltage see datasheet
Minimum bending radius 15x Outer-Ø

Details

Cable Structure

  • Al conductor, stranded acc. to DIN VDE 0295 Class 2 / IEC 60228 Class 2
  • Inner conductive layer
  • Core insulation: XLPE acc. to HD 620 S2 (compound type DIX8)
  • Outer conductive layer
  • Longitudinally waterproof, conductive wrapping
  • Screen: braiding of copper wires with one or two counter helix conductors
  • Longitudinally waterproof wrapping
  • Aluminium wrapping, firmly welded to the outer sheath
  • Outer sheath: PE acc. to HD 620 S2 (compound type DMP2)
  • Sheath colour: black

Properties

  • for outdoor use
  • direct burial
  • the materials used during manufacturing are cadmium-free, contain no silicone and are free from substances harmful to the wetting properties of lacquers

Notes

  • rm = round, stranded conductor
  • the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only
  • the PE outer sheath is not flame retardant acc. to DIN EN 60332-1-2
  • for maximum operational reliability, the core insulation and the outer conductive layer are simultaneously extruded and permanently welded together. For installation, a peeling tool is recommended.

Application

  • Installation primarily for power utility grids and in cable ducts, outdoors, underground and in water, and also on pallets for manufacturing plants, switchgear and power stations. The resistant Al/PE-laminated sheathing acts as a cross water barrier. It inhibits the diffusion of water. In case of sheathing damage, water impact is contained at the flaw. The cable can be severely mechanically stressed during installation and operation. The internal conductive layer between conductor and VPE insulation and the adherent external conductive layer on the VPE insulation guarantees a design with high operational safety and no partial discharge.

All articles NA2XS(FL)2Y

Filter / Sorting

Cross-section (mm²)
Outer diameter
Nominal Voltage
Item description
Part no.
Outer Ø mm (approx.) AWG (approx.) Cu-weight kg/km Al-weight kg/km
NA2XS(FL)2Y 6/10 kV black 1 x 50 rm / 16 mm² 38062 30.0 1 182.0 145.0 view
NA2XS(FL)2Y 12/20 kV black 1 x 50 rm / 16 mm² 38073 35.0 1 182.0 145.0 view
NA2XS(FL)2Y 18/30 kV black 1 x 50 rm / 16 mm² 33084 39.0 1 182.0 145.0 view
NA2XS(FL)2Y 6/10 kV black 1 x 70 rm / 16 mm² 38063 32.0 2/0 182.0 203.0 view
NA2XS(FL)2Y 12/20 kV black 1 x 70 rm / 16 mm² 38074 36.0 2/0 182.0 203.0 view
NA2XS(FL)2Y 18/30 kV black 1 x 70 rm / 16 mm² 33085 40.0 2/0 182.0 203.0 view
NA2XS(FL)2Y 6/10 kV black 1 x 95 rm / 16 mm² 38064 33.0 3/0 182.0 276.0 view
NA2XS(FL)2Y 12/20 kV black 1 x 95 rm / 16 mm² 38075 38.0 3/0 182.0 276.0 view
NA2XS(FL)2Y 18/30 kV black 1 x 95 rm / 16 mm² 38083 42.0 3/0 182.0 276.0 view
NA2XS(FL)2Y 6/10 kV black 1 x 120 rm / 16 mm² 38065 34.0 4/0 182.0 348.0 view
NA2XS(FL)2Y 12/20 kV black 1 x 120 rm / 16 mm² 38076 39.0 4/0 182.0 348.0 view
NA2XS(FL)2Y 18/30 kV black 1 x 120 rm / 16 mm² 38084 44.0 4/0 182.0 348.0 view
NA2XS(FL)2Y 6/10 kV black 1 x 150 rm / 25 mm² 38066 36.0 300 kcmil 283.0 435.0 view
NA2XS(FL)2Y 12/20 kV black 1 x 150 rm / 25 mm² 33089 41.0 300 kcmil 283.0 435.0 view
NA2XS(FL)2Y 18/30 kV black 1 x 150 rm / 25 mm² 38085 45.0 300 kcmil 283.0 435.0 view
NA2XS(FL)2Y 6/10 kV black 1 x 185 rm / 25 mm² 38067 38.0 350 kcmil 283.0 537.0 view
NA2XS(FL)2Y 12/20 kV black 1 x 185 rm / 25 mm² 38077 43.0 350 kcmil 283.0 537.0 view
NA2XS(FL)2Y 18/30 kV black 1 x 185 rm / 25 mm² 38086 47.0 350 kcmil 283.0 537.0 view
NA2XS(FL)2Y 6/10 kV black 1 x 240 rm / 25 mm² 38068 40.0 500 kcmil 283.0 696.0 view
NA2XS(FL)2Y 12/20 kV black 1 x 240 rm / 25 mm² 38078 45.0 500 kcmil 283.0 696.0 view
NA2XS(FL)2Y 18/30 kV black 1 x 240 rm / 25 mm² 38087 49.0 500 kcmil 283.0 696.0 view
NA2XS(FL)2Y 6/10 kV black 1 x 300 rm / 25 mm² 38069 42.0 600 kcmil 283.0 870.0 view
NA2XS(FL)2Y 12/20 kV black 1 x 300 rm / 25 mm² 38079 47.0 600 kcmil 283.0 870.0 view
NA2XS(FL)2Y 18/30 kV black 1 x 300 rm / 25 mm² 38088 52.0 600 kcmil 283.0 870.0 view
NA2XS(FL)2Y 6/10 kV black 1 x 400 rm / 35 mm² 38070 46.0 750 kcmil 394.0 1160.0 view
NA2XS(FL)2Y 12/20 kV black 1 x 400 rm / 35 mm² 38080 50.0 750 kcmil 394.0 1160.0 view
NA2XS(FL)2Y 18/30 kV black 1 x 400 rm / 35 mm² 38089 55.0 750 kcmil 394.0 1160.0 view
NA2XS(FL)2Y 6/10 kV black 1 x 500 rm / 35 mm² 38071 49.0 1000 kcmil 394.0 1450.0 view
NA2XS(FL)2Y 12/20 kV black 1 x 500 rm / 35 mm² 38081 54.0 1000 kcmil 394.0 1450.0 view
NA2XS(FL)2Y 18/30 kV black 1 x 500 rm / 35 mm² 38090 30.0 1000 kcmil 394.0 1450.0 view
NA2XS(FL)2Y 6/10 kV black 1 x 630 rm / 35 mm² 38072 51.0 1250 kcmil 394.0 1827.0 view
NA2XS(FL)2Y 12/20 kV black 1 x 630 rm / 35 mm² 38082 55.0 1250 kcmil 394.0 1827.0 view
NA2XS(FL)2Y 18/30 kV black 1 x 630 rm / 35 mm² 38091 60.0 1250 kcmil 394.0 1827.0 view