HELUDATA® EN-50288-7 XLPE/PVC OSA 300
  • UKCA-Zertifizierung
Artikel

Technische Daten

Instrumentation cable acc. to EN 50288-7
Temperature range flexing -5°C to +50°C
fixed -30°C to +90°C
Nominal voltage U AC 300 V
Test voltage core/core 1500 V
Test voltage core/screen 1500 V
Minimum bending radius fixed 10x Outer-Ø
Insulation resistance > 5000 MΩxkm
Mutual capacitance max. 150 pF/m
Inductance max. 1 mH/km
L/R (ratio) 0.5 mm² < 25 μH/Ω
0.75 mm² < 25 μH/Ω
1 mm² < 25 μH/Ω
1.5 mm² < 40 μH/Ω
2.5 mm² < 60 μH/Ω

Details

Aufbau

  • Copper wire bare, stranded acc. to DIN VDE 0295 Class 2 / IEC 60228 Class 2
  • Core insulation: XLPE acc. to EN 50290-2-29
  • Core identification:
  • pairs: wh, bk
  • triads: wh, bk, rd
  • quads: wh, bk, rd, gy
  • white cores with consecutive labeling in black digits
  • Cores stranded in pairs / triads / quads, cores stranded in cable elements with optimal lay lengths
  • Cable elements are stranded with optimal lay lengths
  • Overall screen: AL/PET tape over tinned copper stranded drain wire (7x0,3 mm)
  • Inner sheath: PVC acc. to EN 50290-2-22
  • Inner sheath colour: like outer sheath
  • Armouring: single layer of galvanised round steel wires acc. to EN 10257-1
  • Outer sheath: PVC acc. to EN 50290-2-22
  • Outer sheath colour: black (RAL 9005) or blue (RAL 5015)
  • Length marking: in metres

Eigenschaften

  • low level of line attenuations and low mutual capacitances enable long transmission distances
  • cable elements are produced of non-hygroscopic materials

Prüfungen

  • flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
  • bundle fire test acc. to DIN VDE 0482-332-3-22 / DIN EN 60332-3-22 / IEC 60332-3-22 (Cat. A, 40 min.)
  • oil-resistant acc. to ICEA S-73-532 / NEMA WC 57
  • UV-resistant acc. to UL 1581 sec. 1200

Hinweise

  • alternative denomination: RE-2X(St)YRY
  • suitable for direct burial
  • the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only
  • we also offer cable glands: HELUTOP® HT-MS-EX-d / e4

Verwendung

  • For the transmission of digital and analog signals in harsh environments like oil, gas and petrochemical industries. The cables are suitable for fixed installation in dry and damp locations, open spaces and in underground networks.

Artikel HELUDATA® EN-50288-7 XLPE/PVC OSA 300

Aderzahl
Anzahl Paare
Nennquerschnitt (mm²)
Außendurchmesser
Mantelfarbe
Item description
Part no.
Outer Ø mm (approx.) Cu-weight kg/km Weight kg/km (approx.) Copper base in EUR / 100 kg

Downloads

Zubehör

Zu diesem Produkt passende Produkte

Info Circlechevron-leftAlertBrowse fileDownload fileFileImagePdfWordTextExcelPowerpointArchiveCsvAudioVideoSpinnerCalendarSort NoneSort ASCSort DESCReturn arrowMinusYouTubeSyncVisibleInvisible