TOPFLEX®-EMV-UV-3-PLUS-2YSLCYK-J UL/CSA black 3 x 70 + 3 G 10 mm²

TOPFLEX®-EMV-UV-3-PLUS-2YSLCYK-J UL/CSA black 3 x 70 + 3 G 10 mm² Part No. 22225
  • UL Certification
  • CSA Certification
  • EAC Certification
  • UV-resistant
  • Length Marking In Meters
  • UKCA Certification
  • protective conductor (GN-YE) divided into thirds
  • UV resistant
  • double shielded
  • EMC-preferred type

Item Details

Part No.
22225
Item description
TOPFLEX®-EMV-UV-3-PLUS-2YSLCYK-J UL/CSA black 3 x 70 + 3 G 10 mm²
AWG (approx.)
2/0
Outer Ø mm (approx.)
35.5
Cu factor per km
2871.0
Weight kg/km (approx.)
3056.0
Weight lb(s)/feet (approx.)
6737.4
Copper base in EUR / 100 kg
150
Feet per Packaging Unit
1640, 3280
Cut-to-length service available
yes
EAN/GTIN
4060892150807
Customs tariff number
85444995

Technical Data

Motor connection cable for frequency converters acc. to UL Std. 758 (AWM) Style 2570, in alignment with DIN VDE 0250
Temperature range flexible -5°C to +80°C
fixed -40°C to +80°C
Nominal voltage UL (AWM) AC 1000 V
Test voltage conductor/conductor 4000 V
Coupling resistance see datasheet
Minimum bend radius flexible
<12 mm: 10x Outer ø
12-20 mm: 15x Outer ø
>20 mm: 20x Outer ø
fixed
<12 mm: 5x Outer ø
12-20 mm: 7.5x Outer ø
>20 mm: 10x Outer ø

Details

Cable Structure

      • Copper wire bare, finely stranded acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
      • Conductor insulation: PE
      • Conductor identification: brown, black, gray, green-yellow (divided into thirds)
      • Ground conductor: GN-YE divided into thirds (3+3 conductor structure)
      • Conductors stranded with optimal lay lengths
      • 1. Shield: plastic-coated aluminum foil (St)
      • 2. Shield: tinned copper braided shield, approx. coverage 85%
      • Outer jacket: Special-PVC
      • Jacket color: black (RAL 9005)
      • Length marking: in meters

Properties

      • resistant to: UV radiation
      • for outdoor use
      • optimal shielding enables interference-free operation of frequency converters
      • low coupling resistance ensures good electromagnetic compatibility
      • low mutual capacitance of the individual conductors due to PE conductor insulation and low shield capacity, enable low power transmission loss

Tests

      • flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2, CSA FT1
      • electromagnetic compatibility acc. to DIN VDE 0875-11 / DIN EN 55011
      • certifications and approvals:
      • EAC

Notes

      • the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only

Application

      • Motor connection cable for fixed installations and applications with occasional free movement involving medium mechanical stress in dry, damp and wet rooms as well as outdoors. For use in the automotive, food processing and packaging industry, in transport belts, machine tools, handling equipment, pumps, as well as in fans and air condition systems. EMC= Electromagnetic Compatibility; in order to optimise EMC properties, we recommend a double-sided and all-round large contact area of the copper braiding.
Info Circlechevron-leftAlertBrowse fileDownload fileFileImagePdfWordTextExcelPowerpointArchiveCsvAudioVideoSpinnerCalendarSort NoneSort ASCSort DESCReturn arrowMinusYouTubeSyncVisibleInvisible