SiHF/GL-P redbrown 2 x 1.5 mm² Part No. 23074
  • EAC Certification
  • Halogen-free (LS0H)
  • UKCA Certification
  • Silicone cable
  • increased temperature resistance
  • tinned wire
  • galvanized steel wire braid to protect against mechanical damage

Item Details

Part No.
23074
Item description
SiHF/GL-P redbrown 2 x 1.5 mm²
AWG (approx.)
16
Outer Ø mm (approx.)
8.7
Cu factor per km
29.0
Weight kg/km (approx.)
127.0
Weight lb(s)/feet (approx.)
280.0
Copper base in EUR / 100 kg
150
Feet per Packaging Unit
328, 1640, 3280
Cut-to-length service available
yes
EAN/GTIN
4060892159145
Customs tariff number
85444995

Technical Data

Silicone control and connection cable in alignment with DIN VDE 0250-1, DIN VDE 0285-525-2-83 / DIN EN 50525-2-83
Temperature range flexible +5°C to +180°C
fixed -60°C to +180°C
Conductor operating temperature +180°C
Nominal voltage AC U0/U 300/500 V
Test voltage conductor/conductor 2000 V
Breakdown voltage 4000 V
Minimum bend radius flexible 10x Outer Ø
fixed 5x Outer Ø

Details

Cable Structure

      • Copper wire tinned, finely stranded acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
      • Conductor insulation: silicone
      • Conductor identification acc. to DIN VDE 0293-308,
      • 2 - 5 conductor(s): color coded
      • 6 - 24 conductor(s): black conductors with consecutive white numbers
      • Ground conductor: starting with 3 conductors,
      • G = with GN-YE ground, in the outer layer,
      • x = without ground conductor
      • Conductors stranded in layers with optimal lay lengths
      • Outer jacket: silicone
      • Jacket color: redbrown
      • Glass silk tape wrap
      • Steel wire braid, galvanized

Properties

      • halogen-free
      • high flash point
      • leaves an insulating layer of SiO2 when exposed to flames
      • no significant changes in dielectric strength and insulation resistance even at higher temperatures

Tests

      • halogen-free acc. to DIN VDE 0482-754-1 / DIN EN 60754-1 / IEC 60754-1
      • combustible gas corrosiveness acc. to DIN VDE 0482-754-2 / DIN EN 60754-2 / IEC 60754-2
      • flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
      • certifications and approvals:
      • EAC

Notes

      • the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only

Application

      • Silicone cables screened with steel braiding were evolved for use wherever insulation is subjected to extreme temperature changes. The good performance of the environmental resistant properties means that silicone cables can be used at temperatures down to -60°C. Silicone cables are halogen-free cables and are especially suited for installation in power stations. They have also found their uses in the steel producing industries, aviation industry, ship building as well as in ceramic, glass and cement factories. Only suitable for use in dry conditions.
Info Circlechevron-leftAlertBrowse fileDownload fileFileImagePdfWordTextExcelPowerpointArchiveCsvAudioVideoSpinnerCalendarSort NoneSort ASCSort DESCReturn arrowMinusYouTubeSyncVisibleInvisible