N2XSH 12/20 kV black 1 x 240 rm / 25 mm²

N2XSH 12/20 kV black 1 x 240 rm / 25 mm² Part No. 11021526
  • VDE Certification
  • Halogen-free (LS0H)
  • Copper conductor
  • XLPE-insulated
  • halogen-free outer jacket
  • 6/10 kV, 12/20 kV, 18/30 kV

Item Details

Part No.
11021526
Item description
N2XSH 12/20 kV black 1 x 240 rm / 25 mm²
AWG (approx.)
500 kcmil
Outer Ø mm (approx.)
38.0 - 44.0
Cu factor per km
2587.0
Weight kg/km (approx.)
3330.0
Weight lb(s)/feet (approx.)
7341.4
Copper base in EUR / 100 kg
0
Feet per Packaging Unit
500, 1000
Cut-to-length service available
yes
EAN/GTIN
4060892522017
Customs tariff number
85446010

Technical Data

Medium-voltage cable acc. to DIN VDE 0276-622, HD 622 S1
Temperature range flexible -5°C to +70°C
fixed -5°C to +70°C
Conductor operating temperature +90°C
Short circuit temperature at the conductor +250°C (Short circuit duration max. 5 s)
Nominal voltage see datasheet
Operating voltage see datasheet
Test voltage see datasheet
Minimum bend radius 15x Outer Ø

Details

Cable Structure

      • Copper conductor bare, stranded acc. to DIN VDE 0295 Class 2 / IEC 60228 Class 2
      • Inner conductive layer
      • Conductor insulation: XLPE acc. to HD 620 S2 (compound type DIX8)
      • Outer conductive layer
      • Conductive wrap
      • Shield: copper wire braiding with one or two counter helix conductors
      • Wrapping
      • Outer jacket: halogen-free polymer
      • Jacket color: black

Properties

      • halogen-free

Tests

      • halogen-free acc. to DIN VDE 0482-754-1 / DIN EN 60754-1 / IEC 60754-1
      • combustible gas corrosiveness acc. to DIN VDE 0482-754-2 / DIN EN 60754-2 / IEC 60754-2
      • flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
      • bundle fire test acc. to DIN VDE 0482-332-3-24 / DIN EN 60332-3-24 / IEC 60332-3-24
      • smoke density acc. to DIN VDE 0482-1034-1+2 / DIN EN 61034-1+2 / IEC 61034-1+2

Notes

      • rm = round, stranded conductor
      • the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only

Application

      • Suitable for indoor installation and in cable ducts, outdoors and in the ground only as protected installation, as well as for installation on cable trays for industrial systems, switch-boards and power stations. Good laying properties favour laying even with difficult routing. The inner conducting layer between the conductor and the XLPE insulation and the firmly bonded outer conducting layer on the XLPE insulation assure a construction free of partial discharges with high operational reliability.