JE-LiHCH Bd gray 2 x 2 x 0.5 mm²
Part No. 34350
- Cables for Industrial Electronics
- stranded conductor
- halogen-free
Item Details JE-LiHCH Bd gray 2 x 2 x 0.5 mm²
- Part No.
- 34350
- Item description
- JE-LiHCH Bd gray 2 x 2 x 0.5 mm²
- AWG (approx.)
- 20
- Outer Ø mm (approx.)
- 6.8
- Cu factor per km
- 44.0
- Weight kg/km (approx.)
- 102.0
- Weight lb(s)/feet (approx.)
- 224.9
- Copper base in EUR / 100 kg
- 100
- CPR class
- Dca, Eca
- Feet per Packaging Unit
- 328, 1640, 3280
- Cut-to-length service available
- yes
- EAN/GTIN
- 4060892100093
- Customs tariff number
- 85444995
Technical Data JE-LiHCH Bd gray 2 x 2 x 0.5 mm²
Data cable in alignment with DIN VDE 0815 | |
Temperature range | flexible -5°C to +50°C fixed -30°C to +70°C |
Peak operating voltage | 225 V (not for high power current installation purposes) |
Test voltage conductor/conductor | 500 V |
Test voltage conductor/shield | 2000 V |
Conductor resistance at 20°C | max. 39.2 Ohm/km |
Mutual capacitance conductor/conductor | at 800 Hz 2 - 4 pairs: approx. 144 pF/m 8 - 40 pairs: approx. 120 pF/m |
Capacitive coupling k1 | at 800 Hz, max. 200 pF/100m; 20% of the values, but at least one value may amount up to 400 pF/100m |
Minimum bend radius | fixed 7.5x Outer Ø |
Details JE-LiHCH Bd gray 2 x 2 x 0.5 mm²
Cable Structure
-
- Copper wire bare, stranded
-
- Wire structure:
- 0.5 mm²: 7 x 0.3 mm
-
- Conductor insulation: halogen-free polymer acc. to DIN VDE 0819-106 / DIN EN 50290-2-26
-
- Conductor identification acc. to. DIN VDE 0815, color coded Ring identification of the bundles
-
- Conductors stranded in pairs with optimal lay lengths, 4 pairs stranded into bundles with optimal lay lengths, bundles stranded in layers with optimal lay lengths
-
- Foil wrap
-
- Shield: tinned copper braided shield
-
- Outer jacket: halogen-free polymer acc. to DIN VDE 0819-107 / DIN EN 50290-2-27
-
- Jacket color: gray (RAL 7032)
Properties
-
- halogen-free
Tests
-
- combustible gas corrosiveness acc. to DIN VDE 0482-754-2 / DIN EN 60754-2 / IEC 60754-2
-
- bundle fire test acc. to DIN VDE 0482-332-3-24 / DIN EN 60332-3-24 / IEC 60332-3-24
-
- smoke density acc. to DIN VDE 0482-1034-1+2 / DIN EN 61034-1+2 / IEC 61034-1+2
-
- certifications and approvals:
- EAC
Notes
-
- the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only
-
- 2-pair cables: conductors stranded in a star quad
Application
-
- Halogen-free installation cables with improved characteristics in the case of fire are used for telephone transmission, measuring and signal purposes. The copper screened design (C) protects the transmission circuits against electrical interferences. A fire propagation is prevented through high oxygen index of the insulation material and produce no corrosive gases in case of fire. They are preferably used for telecommunication installations inside buildings. These cables are suitable for fixed installation in areas with danger of fire, in dry and damp environments as well as in and under plaster. Installation cables are not allowed for purposes of high current and power or burial installation. EMC= Electromagnetic compatibillity; to optimize the EMC features we recommend a large round contact of the copper braiding on both ends.