Y-CY-JB transparent 4 G 120 mm² Part No. 16474
  • EAC Certification
  • Length Marking In Meters
  • UKCA Certification
  • with inner jacket
  • EMC-preferred type

Item Details

Part No.
16474
Item description
Y-CY-JB transparent 4 G 120 mm²
AWG (approx.)
4/0
Outer Ø mm (approx.)
56.7
Cu factor per km
5231.0
Weight kg/km (approx.)
7315.0
Weight lb(s)/feet (approx.)
16126.9
Copper base in EUR / 100 kg
150
CPR class
Eca
Feet per Packaging Unit
1640, 3280
Cut-to-length service available
yes
EAN/GTIN
4060892025129
Customs tariff number
85444995

Technical Data

PVC control and connection cable in alignment with DIN VDE 0285-525-2-51 / DIN EN 50525-2-51
Temperature range flexible -15°C to +80°C
fixed -40°C to +80°C
Nominal voltage 0.5 - 1.5 mm²: AC U0/U 300/500 V
2.5 - 185 mm²: AC U0/U 450/750 V
2.5 - 185 mm²: static and protected installation AC U0/U 600/1000 V
Test voltage conductor/conductor 4000 V
Test voltage conductor/shield 2000 V
Coupling resistance at 30 MHz, approx. 250 Ohm/km
Minimum bend radius flexible 10x Outer Ø
fixed 5x Outer Ø

Details

Cable Structure

      • Copper wire bare, finely stranded acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
      • Conductor insulation: Special-PVC
      • Conductor identification acc. to JB/OB color code, color coded
      • Ground conductor: starting with 3 conductors,
      • G = with GN-YE ground (JB),
      • X = without ground conductor (OB)
      • Conductors stranded with optimal lay lengths
      • Inner jacket: PVC acc. to DIN VDE 0207-363-4-1 / DIN EN 50363-4-1 (compound type TM2)
      • Shield: tinned copper braided shield, approx. coverage 85%
      • Outer jacket: PVC acc. to DIN VDE 0207-363-4-1 / DIN EN 50363-4-1 (compound type TM2)
      • Jacket color: transparent
      • Length marking: in meters

Properties

      • largely resistant to: oil,
      • for details, see "Technical Information"

Tests

      • flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
      • certifications and approvals:
      • EAC

Notes

      • the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only

Application

      • Used for flexible applications involving medium mechanical stress with free movement, without tensile stress and without forced motion control in dry rooms, however, not suitable for outdoor use. Used as a connection and control cable in measurement and control technology, in machine and machine tool construction, in conveyers and production lines, in computers, as well as signal cables in electronics. Due to the high screening density, interference-free transmission of signals or pulses is ensured. The PVC inner sheath increases the mechanical load capacity of the cable; the transparent PVC outer sheath makes the tinned copper braid optically effective. EMC = Electromagnetic Compatibility; in order to optimise EMC properties, we recommend a double-sided and all-round large contact area of the copper braiding.
Info Circlechevron-leftAlertBrowse fileDownload fileFileImagePdfWordTextExcelPowerpointArchiveCsvAudioVideoSpinnerCalendarSort NoneSort ASCSort DESCReturn arrowMinusYouTubeSyncVisibleInvisible