Y-CY-JB transparent 3 G 1 mm²
Part No. 16130
- with inner jacket
- EMC-preferred type
Item Details Y-CY-JB transparent 3 G 1 mm²
- Part No.
- 16130
- Item description
- Y-CY-JB transparent 3 G 1 mm²
- AWG (approx.)
- 18
- Outer Ø mm (approx.)
- 8.6
- Cu factor per km
- 64.0
- Weight kg/km (approx.)
- 103.0
- Copper base in EUR / 100 kg
- 150
- CPR class
- Eca
- Feet per Packaging Unit
- 328, 1640, 3280
- Cut-to-length service available
- yes
- EAN/GTIN
- 4060892024788
- Customs tariff number
- 85444995
Technical Data Y-CY-JB transparent 3 G 1 mm²
PVC control and connection cable in alignment with DIN VDE 0285-525-2-51 / DIN EN 50525-2-51 | |
Temperature range | flexible -15°C to +80°C fixed -40°C to +80°C |
Nominal voltage | 0.5 - 1.5 mm²: AC U0/U 300/500 V 2.5 - 185 mm²: AC U0/U 450/750 V 2.5 - 185 mm²: static and protected installation AC U0/U 600/1000 V |
Test voltage conductor/conductor | 4000 V |
Test voltage conductor/shield | 2000 V |
Coupling resistance | at 30 MHz, approx. 250 Ohm/km |
Minimum bend radius | flexible 10x Outer Ø fixed 5x Outer Ø |
Details Y-CY-JB transparent 3 G 1 mm²
Cable Structure
-
- Copper wire bare, finely stranded acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
-
- Conductor insulation: Special-PVC
-
- Conductor identification acc. to JB/OB color code, color coded
-
- Ground conductor: starting with 3 conductors,
- G = with GN-YE ground (JB),
- X = without ground conductor (OB)
-
- Conductors stranded with optimal lay lengths
-
- Inner jacket: PVC acc. to DIN VDE 0207-363-4-1 / DIN EN 50363-4-1 (compound type TM2)
-
- Shield: tinned copper braided shield, approx. coverage 85%
-
- Outer jacket: PVC acc. to DIN VDE 0207-363-4-1 / DIN EN 50363-4-1 (compound type TM2)
-
- Jacket color: transparent
-
- Length marking: in meters
Properties
-
- largely resistant to: oil,
- for details, see "Technical Information"
Tests
-
- flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
-
- certifications and approvals:
- EAC
Notes
-
- the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only
Application
-
- Used for flexible applications involving medium mechanical stress with free movement, without tensile stress and without forced motion control in dry rooms, however, not suitable for outdoor use. Used as a connection and control cable in measurement and control technology, in machine and machine tool construction, in conveyers and production lines, in computers, as well as signal cables in electronics. Due to the high screening density, interference-free transmission of signals or pulses is ensured. The PVC inner sheath increases the mechanical load capacity of the cable; the transparent PVC outer sheath makes the tinned copper braid optically effective. EMC = Electromagnetic Compatibility; in order to optimise EMC properties, we recommend a double-sided and all-round large contact area of the copper braiding.