THERMFLEX® 180 EWKF-C black 20 G 1.5 mm² Part No. 79818
  • EAC Certification
  • Halogen-free (LS0H)
  • Length Marking In Meters
  • UKCA Certification
  • Silicone cable
  • temperature-resistant
  • increased mechanical strength
  • EMC-preferred type

Item Details

Part No.
79818
Item description
THERMFLEX® 180 EWKF-C black 20 G 1.5 mm²
AWG (approx.)
16
Outer Ø mm (approx.)
21.4
Cu factor per km
405.1
Weight kg/km (approx.)
766.0
Weight lb(s)/feet (approx.)
1688.7
Copper base in EUR / 100 kg
150
Feet per Packaging Unit
1640, 3280
Cut-to-length service available
yes
EAN/GTIN
4060892159589
Customs tariff number
85444995

Technical Data

Silicone control and connection cable in alignment with DIN VDE 0285-525-2-83 / DIN EN 50525-2-83
Temperature range flexible -25°C to +180°C
fixed -60°C to +180°C
Nominal voltage AC U0/U 300/500 V
Test voltage conductor/conductor 2000 V
Coupling resistance at 30 MHz, approx. 250 Ohm/km
Minimum bend radius flexible 10x Outer Ø
fixed 5x Outer Ø

Details

Cable Structure

      • Copper wire tinned, finely stranded acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
      • Conductor insulation: silicone
      • Conductor identification acc. to DIN VDE 0293-308,
      • 2 - 5 conductor(s): color coded
      • 7 - 20 conductor(s): black conductors with consecutive white numbers
      • Ground conductor: starting with 3 conductors,
      • G = with GN-YE ground, in the outer layer,
      • x = without ground conductor (OZ)
      • Conductors stranded in layers with optimal lay lengths
      • Inner jacket: silicone
      • Shield: tinned copper braided shield, approx. coverage 85%
      • Foil wrap
      • Outer jacket: special silicone
      • Jacket color: black (RAL 9005)
      • Length marking: in meters

Properties

      • resistant to: ozone, oxygen, weathering effects, alcohols, diluted acids, alkalis, saline solutions, oxidizing agents, high molecular weight oils, vegetable and animal fats, plasticizers and clophen, seawater
      • abrasion-resistant, notch-resistant, tear-resistant
      • for outdoor use
      • halogen-free
      • high flash point
      • leaves an insulating layer of SiO2 when exposed to flames
      • no significant changes in dielectric strength and insulation resistance even at higher temperatures

Tests

      • halogen-free acc. to DIN VDE 0482-754-1 / DIN EN 60754-1 / IEC 60754-1
      • combustible gas corrosiveness acc. to DIN VDE 0482-754-2 / DIN EN 60754-2 / IEC 60754-2
      • flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
      • certifications and approvals:
      • EAC

Notes

      • the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only

Application

      • Halogen-free silicone cable for applications that require an increased mechanical strength as well as a higher temperature resistance. For use in dry, damp and wet rooms as well as outdoors. Suitable for use in air conditioning and heating systems, in saunas and solariums, in foundries, in steel, cement and ceramic plants as well as in furnaces and lighting fixtures. An interference-free transmission of signals and pulse is assured by the high screening density. EMC = Electromagnetic Compatibility; in order to optimise EMC properties, we recommend a double-sided and all-round large contact area of the copper braiding.
Info Circlechevron-leftAlertBrowse fileDownload fileFileImagePdfWordTextExcelPowerpointArchiveCsvAudioVideoSpinnerCalendarSort NoneSort ASCSort DESCReturn arrowMinusYouTubeSyncVisibleInvisible