PAAR-TRONIC gray 38 x 2 x 0.14 mm² Part No. 19027
  • EAC Certification
  • Length Marking In Meters
  • UKCA Certification
  • color code DIN 47100
  • for flexible use where structural or design conditions require small outer diameters

Item Details

Part No.
19027
Item description
PAAR-TRONIC gray 38 x 2 x 0.14 mm²
AWG (approx.)
26
Outer Ø mm (approx.)
14.2
Cu factor per km
102.0
Weight kg/km (approx.)
272.0
Weight lb(s)/feet (approx.)
599.7
Copper base in EUR / 100 kg
150
CPR class
Eca
Feet per Packaging Unit
328, 1640, 3280
Cut-to-length service available
yes
EAN/GTIN
4060892081460
Customs tariff number
85444995

Technical Data

PVC data cable in alignment with DIN VDE 0812
Temperature range flexible -5°C to +80°C
fixed -30°C to +80°C
Peak operating voltage 350 V (not for high power current installation purposes)
Test voltage conductor/conductor 1200 V
Breakdown voltage 2400 V
Mutual capacitance conductor/conductor at 800 Hz
0.14 - 0.25 mm²: approx. 100 pF/m
0.34 - 0.75 mm²: approx. 150 pF/m
Capacitive coupling k1 at 800 Hz, max. 300 pF/100m
Characteristic impedance 78 Ohm,
(approx. value)
Inductance approx. 0.65 mH/km
Minimum bend radius flexible 7.5x Outer Ø
fixed 4x Outer Ø

Details

Cable Structure

      • Copper wire bare, 0.5 - 0.75 mm²: finely stranded acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
      • Wire structure:
      • 0.14 mm²: approx. 18 x 0.1 mm
      • 0.25 mm²: approx. 14 x 0.15 mm
      • 0.34 mm²: 7 x 0.25 mm
      • Conductor insulation: PVC acc. to DIN VDE 0207-363-3 / DIN EN 50363-3 (compound type TI2)
      • Conductor identification acc. to DIN 47100 (paired stranding), color coded
      • x = without ground conductor
      • Conductors stranded in pairs with optimal lay lengths, Pairs stranded in layers with optimal lay lengths
      • Foil wrap
      • Outer jacket: PVC acc. to DIN VDE 0207-363-4-1 / DIN EN 50363-4-1 (compound type TM2)
      • Jacket color: gray (RAL 7032)
      • Length marking: in meters

Properties

      • largely resistant to: oil,
      • for details, see "Technical Information"

Tests

      • flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
      • certifications and approvals:
      • EAC

Notes

      • the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only

Application

      • Suitable for flexible applications with free movement, without tensile stress and without forced motion control in dry, damp and wet rooms, however, not suitable for outdoor use. Used as a control and signal cable in electronic engineering, measurement and control technology and wherever wiring must be executed using the smallest possible outside diameter, with consideration of electronic possibilities, e.g. computer systems, signal technology, scales etc.