PAAR-TRONIC-CY gray 10 x 2 x 0.25 mm²
Part No. 21041
- color code DIN 47100
- with drain wire
- EMC-preferred type
Item Details PAAR-TRONIC-CY gray 10 x 2 x 0.25 mm²
- Part No.
- 21041
- Item description
- PAAR-TRONIC-CY gray 10 x 2 x 0.25 mm²
- AWG (approx.)
- 24
- Outer Ø mm (approx.)
- 11.3
- Cu factor per km
- 110.0
- Weight kg/km (approx.)
- 157.0
- Copper base in EUR / 100 kg
- 150
- CPR class
- Eca
- Feet per Packaging Unit
- 328, 1640, 3280
- Cut-to-length service available
- yes
- EAN/GTIN
- 4060892090097
- Customs tariff number
- 85444995
Technical Data PAAR-TRONIC-CY gray 10 x 2 x 0.25 mm²
PVC data cable in alignment with DIN VDE 0812 | |
Temperature range | flexible -5°C to +80°C fixed -30°C to +80°C |
Peak operating voltage | 350 V (not for high power current installation purposes) |
Test voltage conductor/conductor | 1200 V |
Test voltage conductor/shield | 800 V |
Breakdown voltage | 2400 V |
Mutual capacitance conductor/conductor | at 800 Hz 0.14 - 0.25 mm²: approx. 100 pF/m 0.34 - 1.5 mm²: approx. 150 pF/m |
Mutual capacitance conductor/shield | at 800 Hz 0.14 mm²: approx. 240 pF/m 0.25 mm²: approx. 270 pF/m |
Capacitive coupling k1 | at 800 Hz, max. 300 pF/100m |
Characteristic impedance | 78 Ohm, (approx. value) |
Inductance | approx. 0.65 mH/km |
Coupling resistance | at 30 MHz, approx. 250 Ohm/km |
Minimum bend radius | flexible 10x Outer Ø fixed 5x Outer Ø |
Details PAAR-TRONIC-CY gray 10 x 2 x 0.25 mm²
Cable Structure
-
- Copper wire bare, 0.5 - 1.5 mm²: finely stranded acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
-
- Wire structure:
- 0.14 mm²: approx. 18 x 0.1 mm
- 0.25 mm²: approx. 14 x 0.15 mm
- 0.34 mm²: 7 x 0.25 mm
-
- Conductor insulation: PVC acc. to DIN VDE 0207-363-3 / DIN EN 50363-3 (compound type TI2)
-
- Conductor identification acc. to DIN 47100 (paired stranding), color coded
-
- x = without ground conductor
-
- Conductors stranded in pairs with optimal lay lengths, Pairs stranded in layers with optimal lay lengths
-
- Foil wrap
-
- Drain wire, tinned copper
-
- Shield: tinned copper braided shield, approx. coverage 85%
-
- Outer jacket: PVC acc. to DIN VDE 0207-363-4-1 / DIN EN 50363-4-1 (compound type TM2)
-
- Jacket color: gray (RAL 7032)
-
- Length marking: in meters
Properties
-
- largely resistant to: oil,
- for details, see "Technical Information"
Tests
-
- flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
-
- certifications and approvals:
- EAC
Notes
-
- the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only
Application
-
- Suitable for flexible applications with free movement, without tensile stress and without forced motion control in dry, damp and wet rooms, however, not suitable for outdoor use. Used as control and signal cables for systems at risk of interference radiation. Due to the dense braided screening, interference through parallel running cables is suppressed and as a result of the pair stranding, favourable crosstalk attenuation values are achieved. EMC= Electromagnetic Compatibility; in order to optimise EMC properties, we recommend a double-sided and all-round large contact area of the copper braiding.