NA2XSY 6/10 kV red 1 x 400 rm / 35 mm² Part No. 32451
  • VDE Certification
  • Al conductor
  • XLPE-insulated
  • PVC jacket
  • 6/10 kV, 12/20 kV, 18/30 kV

Item Details

Part No.
32451
Item description
NA2XSY 6/10 kV red 1 x 400 rm / 35 mm²
AWG (approx.)
750 kcmil
Outer Ø mm (approx.)
40.0 - 45.0
Cu factor per km
394.0
Al factor per km
1160.0
Weight kg/km (approx.)
2315.0
Weight lb(s)/feet (approx.)
5103.7
Copper base in EUR / 100 kg
0
Aluminum base in EUR / 100 kg
0
Feet per Packaging Unit
1640, 3280
Cut-to-length service available
yes
EAN/GTIN
4060892276750
Customs tariff number
85446090

Technical Data

Medium-voltage cable acc. to DIN VDE 0276-620, HD 620 S2, IEC 60502
Temperature range during installation -5°C
Conductor operating temperature +90°C
Short circuit temperature at the conductor +250°C (Short circuit duration max. 5 s)
Nominal voltage see datasheet
Operating voltage see datasheet
Test voltage see datasheet
Minimum bend radius 15x Outer Ø

Details

Cable Structure

      • Al conductor, stranded acc. to DIN VDE 0295 Class 2 / IEC 60228 Class 2
      • Inner conductive layer
      • Conductor insulation: XLPE acc. to HD 620 S2 (compound type DIX8)
      • Outer conductive layer
      • Conductive wrap
      • Shield: copper wire braiding with one or two counter helix conductors
      • Wrapping
      • Outer jacket: PVC acc. to HD 620 S2 (compound type DMV6)
      • Jacket color: red

Properties

      • direct burial

Tests

      • flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2

Notes

      • rm = round, stranded conductor
      • the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only
      • Part no. 32444, 32446, 32448, 32457, 32459, 32461, 32470, 32472, 32474: approved exclusively for direct burial

Application

      • Suitable for installation mostly for power supply stations, in indoors and in cable ducts, outdoor with protected laying, underground and in water as well as for installation on cable trays for industries, switch-boards and power stations. Due to the good laying characteristic, this can also be laid easily in difficult line guideways. The inner conducting layer between the conductor and the XLPE insulation and the firmly bonded outer conducting layer on the XLPE insulation assures a construction free of partial discharges with high operational reliability.