LiY-TPC-Y gray 3 x 2 x 0.5 mm² Part No. 21356
  • EAC Certification
  • Length Marking In Meters
  • UKCA Certification
  • color code DIN 47100
  • shielded pairs
  • EMC-preferred type

Item Details

Part No.
21356
Item description
LiY-TPC-Y gray 3 x 2 x 0.5 mm²
AWG (approx.)
20
Outer Ø mm (approx.)
9.2
Cu factor per km
87.0
Weight kg/km (approx.)
136.0
Weight lb(s)/feet (approx.)
299.8
Copper base in EUR / 100 kg
150
Feet per Packaging Unit
328, 1640, 3280
Cut-to-length service available
yes
EAN/GTIN
4060892091650
Customs tariff number
85444995

Technical Data

PVC data cable in alignment with DIN VDE 0812
Temperature range flexible -5°C to +70°C
fixed -30°C to +70°C
Peak operating voltage 500 V (not for high power current installation purposes)
Test voltage conductor/conductor 1200 V
Breakdown voltage 2400 V
Coupling resistance at 30 MHz, approx. 250 Ohm/km
Minimum bend radius flexible 12x Outer Ø
fixed 7.5x Outer Ø

Details

Cable Structure

      • Copper wire bare, 0.5 - 1 mm²: finely stranded acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
      • Wire structure:
      • 0.25 mm²: approx. 14 x 0.15 mm
      • 0.34 mm²: 7 x 0.25 mm
      • Conductor insulation: PVC acc. to DIN VDE 0207-363-3 / DIN EN 50363-3 (compound type TI2)
      • Conductor identification acc. to DIN 47100 (paired stranding), color coded
      • x = without ground conductor
      • Conductors stranded in pairs with optimal lay lengths
      • Foil wrap of the pairs
      • Shielding element: pairs, tinned copper braided shield, approx. coverage 85%
      • Pairs stranded in layers with optimal lay lengths
      • Foil wrap
      • Outer jacket: PVC acc. to DIN VDE 0207-363-4-1 / DIN EN 50363-4-1 (compound type TM2)
      • Jacket color: gray (RAL 7032)
      • Length marking: in meters

Properties

      • largely resistant to: oil,
      • for details, see "Technical Information"

Tests

      • flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
      • certifications and approvals:
      • EAC

Notes

      • the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only

Application

      • The pair screened data transmission cable is used as a control and signal cable in electronics and in measurement and control technology. It provides interference-free transmission of data signals from peripheral equipment to information storage. Excellent connection cable for sound mixers, studio equipment and measurement and control technology. Reliable in process control, machining centres and safety engineering systems. These cables with copper screening are ideally suited for interefence-free data and signal transmission for measurement and control technology. EMC= Electromagnetic Compatibility; in order to optimise EMC properties, we recommend a double-sided and all-round large contact area of the copper braiding.
Info Circlechevron-leftAlertBrowse fileDownload fileFileImagePdfWordTextExcelPowerpointArchiveCsvAudioVideoSpinnerCalendarSort NoneSort ASCSort DESCReturn arrowMinusYouTubeSyncVisibleInvisible