JZ-602 gray 12 G 1 mm² Part No. 83085
  • UL Certification
  • CSA Certification
  • EAC Certification
  • Length Marking In Meters
  • UKCA Certification
  • +90°C
  • 600 V

Item Details

Part No.
83085
Item description
JZ-602 gray 12 G 1 mm²
AWG (approx.)
18
Outer Ø mm (approx.)
10.6
Cu factor per km
115.2
Weight kg/km (approx.)
198.0
Weight lb(s)/feet (approx.)
436.5
Copper base in EUR / 100 kg
150
Feet per Packaging Unit
328, 1640, 3280
Cut-to-length service available
yes
EAN/GTIN
4060892014598
Customs tariff number
85444995

Technical Data

PVC control and connection cable acc. to UL Std. 758 (AWM) Style 2587, CSA Std. C22.2 No. 210 - AWM I/II A/B
Temperature range flexible -10°C to +90°C
fixed -40°C to +90°C
Nominal voltage UL (AWM) AC 600 V
Test voltage conductor/conductor 3000 V
Breakdown voltage 6000 V
Minimum bend radius flexible 7.5x Outer Ø
fixed 4x Outer Ø

Details

Cable Structure

      • Copper wire bare, finely stranded acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
      • Conductor insulation: PVC acc. to UL Std. 758 (AWM) Style 11008, CSA Std. C22.2 No. 210
      • Conductor identification acc. to DIN VDE 0293-334, black conductors with consecutive white numbers
      • Ground conductor: starting with 3 conductors,
      • G = with GN-YE ground, in the outer layer,
      • x = without ground conductor (OZ)
      • Conductors stranded in layers with optimal lay lengths
      • Outer jacket: PVC acc. to UL Std. 758 (AWM) Style 2587, CSA Std. C22.2 No. 210
      • Jacket color: gray (RAL 7001)
      • Length marking: in meters

Properties

      • largely resistant to: oil

Tests

      • flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2, UL VW-1, CSA FT1
      • certifications and approvals:
      • EAC

Notes

      • the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only

Application

      • UL/CSA approved, flexible control cable (up to 600 V) for machine, tool and plant construction. Suitable for medium mechanical stress with free movement, without tensile stress and without forced motion control in dry, damp and wet rooms, however, not suitable for outdoor use.