JB-750-GELB yellow 3 G 1.5 mm² Part No. 10334
  • EAC Certification
  • Length Marking In Meters
  • UKCA Certification
  • control and connection cable for hazard warning
  • largely oil resistant

Item Details

Part No.
10334
Item description
JB-750-GELB yellow 3 G 1.5 mm²
AWG (approx.)
16
Outer Ø mm (approx.)
7.8
Cu factor per km
43.0
Weight kg/km (approx.)
100.0
Weight lb(s)/feet (approx.)
220.5
Copper base in EUR / 100 kg
150
Feet per Packaging Unit
328, 1640, 3280
Cut-to-length service available
yes
EAN/GTIN
4060892007156
Customs tariff number
85444995

Technical Data

PVC control cable in alignment with DIN VDE 0285-525-2-11 / DIN EN 50525-2-11
Temperature range flexible -15°C to +80°C
fixed -40°C to +80°C
Nominal voltage AC U0/U 450/750 V
Test voltage conductor/conductor 4000 V
Breakdown voltage 8000 V
Minimum bend radius flexible 7.5x Outer Ø
fixed 4x Outer Ø

Details

Cable Structure

      • Copper wire bare, finely stranded acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
      • Conductor insulation: PVC acc. to DIN VDE 0207-363-3 / DIN EN 50363-3 (compound type TI2)
      • Conductor identification acc. to DIN VDE 0293-308, color coded
      • G = with GN-YE ground
      • Conductors stranded with optimal lay lengths
      • Outer jacket: PVC acc. to DIN VDE 0207-363-4-1 / DIN EN 50363-4-1 (compound type TM2)
      • Jacket color: yellow (RAL 1016)
      • Length marking: in meters

Properties

      • largely resistant to: oil,
      • for details, see "Technical Information"

Tests

      • flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
      • certifications and approvals:
      • EAC

Notes

      • the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only

Application

      • Used for flexible applications involving medium mechanical stress with free movement, without tensile stress and without forced motion control in dry, damp and wet rooms, however, not suitable for outdoor use. Used as a control cable with a yellow outer sheath as a special warning indication. Recommendation following EN 60204 Part 1 or DIN VDE 0113 Part 1.
Info Circlechevron-leftAlertBrowse fileDownload fileFileImagePdfWordTextExcelPowerpointArchiveCsvAudioVideoSpinnerCalendarSort NoneSort ASCSort DESCReturn arrowMinusYouTubeSyncVisibleInvisible