HELUDATA® PAAR-TRONIC 2464 / 300 BLACK 8 x 2 x 20 AWG Part No. 65275
  • UL Certification
  • CSA Certification
  • UL Style 2464
  • 300 V
  • 80°C

Item Details

Part No.
65275
Item description
HELUDATA® PAAR-TRONIC 2464 / 300 BLACK 8 x 2 x 20 AWG
Jacket color
black (RAL 9005)
Cross-sec. mm² (approx.)
0.56
Outer Ø mm (approx.)
10.9
Cu factor per km
86.1
Weight kg/km (approx.)
262.0
Weight lb(s)/feet (approx.)
577.6
Copper base in EUR / 100 kg
150
Feet per Packaging Unit
328, 1640, 3280
Cut-to-length service available
yes
EAN/GTIN
4060892084300
Customs tariff number
85444995

Technical Data

PVC data cable acc. to UL Std. 758 (AWM) Style 2464, CSA Std. C22.2 No. 210 - AWM I/II A/B
Temperature range flexible -10°C to +80°C
fixed -40°C to +80°C
Nominal voltage UL (AWM) AC 300 V
Test voltage conductor/conductor 1500 V
Breakdown voltage 3000 V
Minimum bend radius flexible 15x Outer Ø
fixed 7.5x Outer Ø

Details

Cable Structure

      • Copper wire tinned, finely stranded, AWG sizes
      • Wire structure:
      • 26 AWG: 7 x 0.160 mm
      • 24 AWG: 7 x 0.203 mm
      • 22 AWG: 7 x 0.254 mm
      • 20 AWG: 7 x 0.320 mm
      • Conductor insulation: semirigid PVC acc. to UL Std. 1581 Tab. 50.183
      • Conductor identification: see datasheet
      • x = without ground conductor
      • Conductors stranded in pairs with optimal lay lengths, Pairs stranded in layers with optimal lay lengths
      • Foil wrap
      • Outer jacket: PVC acc. to UL Std. 1581 Tab. 50.182, CSA Std. C22.2 No. 210
      • Jacket color: see datasheet

Properties

      • resistant to: oil, solvents, acids, alkalis

Tests

      • flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2, UL VW-1, CSA FT1

Notes

      • Conductor sizes are based on the AWG measurement system, metric conductor sizes (mm²) are approximated and are for reference only

Application

      • UL/CSA approved, twisted pair data cable for use as a signal and measuring cable in machine tools, assembly lines, conveyor belts, plant construction, air conditioning devices, metallurgical plants, steel mills.
Info Circlechevron-leftAlertBrowse fileDownload fileFileImagePdfWordTextExcelPowerpointArchiveCsvAudioVideoSpinnerCalendarSort NoneSort ASCSort DESCReturn arrowMinusYouTubeSyncVisibleInvisible