H07G-K green-yellow 1 G 95 mm²

H07G-K green-yellow 1 G 95 mm² Part No. 56311
  • HAR Certification
  • EAC Certification
  • UKCA Certification
  • Rubber single conductor
  • finely stranded
  • tinned wire

Item Details

Part No.
56311
Item description
H07G-K green-yellow 1 G 95 mm²
AWG (approx.)
3/0
Outer Ø mm (approx.)
15.5 - 19.3
Cu factor per km
912.0
Weight kg/km (approx.)
937.0
Weight lb(s)/feet (approx.)
2065.7
Copper base in EUR / 100 kg
150
Feet per Packaging Unit
1640, 3280
Cut-to-length service available
yes
EAN/GTIN
4060892240713
Customs tariff number
85444995

Technical Data

Rubber single conductor, H07G-K acc. to DIN VDE 0285-525-2-42 / DIN EN 50525-2-42; 07G-K in alignment with DIN VDE 0285-525-2-42 / DIN EN 50525-2-42
Temperature range flexible -5°C
fixed -40°C
Conductor operating temperature +110°C
Nominal voltage AC U0/U 450/750 V
Test voltage 2500 V
Minimum bend radius fixed
<8 mm: 4x Outer ø
8-12 mm: 5x Outer ø
>12 mm: 6x Outer ø

Details

Cable Structure

      • Copper wire tinned, finely stranded acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
      • 10 - 120 mm²: Foil wrap
      • Conductor insulation: rubber (EVA) acc. to DIN VDE 0207-363-1 / DIN EN 50363-1 (compound type EI3)
      • Conductor identification: see datasheet

Tests

      • certifications and approvals:
      • H07G-K: HAR
      • H07G-K: EAC

Notes

      • the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only
      • Approved conductor colors: black, green-yellow, blue, brown, white, gray, violet, pink, orange, turquoise

Application

      • For installation in electrical conduits as well as in open or closed trunking systems. Used for internal wiring of devices and equipment. Must not come into contact with water.
Info Circlechevron-leftAlertBrowse fileDownload fileFileImagePdfWordTextExcelPowerpointArchiveCsvAudioVideoSpinnerCalendarSort NoneSort ASCSort DESCReturn arrowMinusYouTubeSyncVisibleInvisible