H05VVC4V5-K gray 5 G 1 mm²
Part No. 13086
- oil resistant
- with PVC inner jacket for increased mechanical strength
- EMC-preferred type
- versatile use in many industries, particularly in machine building and plant engineering
Item Details H05VVC4V5-K gray 5 G 1 mm²
- Part No.
- 13086
- Item description
- H05VVC4V5-K gray 5 G 1 mm²
- AWG (approx.)
- 18
- Outer Ø mm (approx.)
- 10.3 - 12.8
- Cu factor per km
- 89.0
- Weight kg/km (approx.)
- 205.0
- Weight lb(s)/feet (approx.)
- 451.9
- Copper base in EUR / 100 kg
- 150
- CPR class
- Eca
- Feet per Packaging Unit
- 328, 1640, 3280
- Cut-to-length service available
- yes
- EAN/GTIN
- 4060892028809
- Customs tariff number
- 85444995
- Alternative cable designation
- NYSLYCYÖ-JZ
Technical Data H05VVC4V5-K gray 5 G 1 mm²
PVC control cable acc. to DIN VDE 0285-525-2-51 / DIN EN 50525-2-51, IEC 60227-74 | |
Temperature range | flexible -5°C to +70°C fixed -40°C to +70°C |
Nominal voltage | AC U0/U 300/500 V |
Test voltage conductor/conductor | 2000 V |
Test voltage conductor/shield | 2000 V |
Breakdown voltage | 4000 V |
Coupling resistance | at 30 MHz, max. 250 Ohm/km |
Minimum bend radius | flexible 10x Outer Ø fixed 5x Outer Ø |
Details H05VVC4V5-K gray 5 G 1 mm²
Cable Structure
-
- Copper wire bare, finely stranded acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
-
- Conductor insulation: PVC acc. to DIN VDE 0207-363-3 / DIN EN 50363-3 (compound type TI2)
-
- Conductor identification acc. to DIN VDE 0293-334, black conductors with consecutive white numbers
-
- Ground conductor: starting with 3 conductors,
- G = with GN-YE ground, in the outer layer,
- x = without ground conductor (OZ)
-
- Conductors stranded in layers with optimal lay lengths
-
- Inner jacket: PVC acc. to DIN VDE 0207-363-4-1 / DIN EN 50363-4-1 (compound type TM2)
-
- Shield: tinned copper braided shield, approx. coverage 85%
-
- Outer jacket: oil-resistant special PVC acc. to DIN VDE 0207-363-4-1 / DIN EN 50363-4-1 (compound type TM5)
-
- Jacket color: gray (RAL 7001)
Properties
-
- resistant to: oil
Tests
-
- flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
-
- oil-resistant acc. to DIN VDE 0473-811-404 / DIN EN 60811-404 / IEC 60811-404
-
- certifications and approvals:
- HAR
- EAC
Notes
-
- the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only
Application
-
- Used for flexible applications involving medium mechanical stress with free movement, without tensile stress and without forced motion control in dry, damp and wet rooms, however, not suitable for outdoor use as a connection cable in machine and machine tool construction, assembly lines, conveyers and production lines. Even various chemical compounds cannot harm the cable. As a cable suitable for damp rooms, it is also preferred for the operation of machines in breweries, bottling plants and car washes. For interference-free data signal transmission in measurement and control technology in case electromagnetic screening is required. The cables may engage in flexible movement after installation, provided the cables are not mechanically overloaded during the movements. These shielded cables are not designed for permanent bending stresses. EMC= Electromagnetic Compatibility; in order to optimise EMC properties, we recommend a double-sided and all-round large contact area of the copper braiding.