F-CY-OZ gray 10 x 0.75 mm²
Part No. 16565
- EMC-preferred type
Item Details F-CY-OZ gray 10 x 0.75 mm²
- Part No.
- 16565
- Item description
- F-CY-OZ gray 10 x 0.75 mm²
- AWG (approx.)
- 19
- Outer Ø mm (approx.)
- 10.7
- Cu factor per km
- 137.0
- Weight kg/km (approx.)
- 180.0
- Weight lb(s)/feet (approx.)
- 396.8
- Copper base in EUR / 100 kg
- 150
- CPR class
- Eca
- Feet per Packaging Unit
- 328, 1640, 3280
- Cut-to-length service available
- yes
- EAN/GTIN
- 4060892021787
- Customs tariff number
- 85444995
Technical Data F-CY-OZ gray 10 x 0.75 mm²
PVC control and connection cable in alignment with DIN VDE 0285-525-2-51 / DIN EN 50525-2-51 | |
Temperature range | flexible -10°C to +80°C fixed -40°C to +80°C |
Nominal voltage | AC U0/U 300/500 V |
Test voltage conductor/conductor | 4000 V |
Test voltage conductor/shield | 2000 V |
Breakdown voltage | 8000 V |
Mutual capacitance conductor/conductor | at 800 Hz 0.5 - 2.5 mm²: approx. 150 pF/m |
Mutual capacitance conductor/shield | at 800 Hz 0.5 - 2.5 mm²: approx. 270 pF/m |
Coupling resistance | at 30 MHz, approx. 250 Ohm/km |
Minimum bend radius | flexible 10x Outer Ø fixed 5x Outer Ø |
Details F-CY-OZ gray 10 x 0.75 mm²
Cable Structure
-
- Copper wire bare, finely stranded acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
-
- Conductor insulation: PVC, compound type Z 7225
-
- Conductor identification acc. to DIN VDE 0293-334, black conductors with consecutive white numbers
-
- Ground conductor: starting with 3 conductors,
- G = with GN-YE ground, in the outer layer,
- x = without ground conductor (OZ)
-
- Conductors stranded in layers with optimal lay lengths
-
- Foil wrap
-
- Shield:
- 1 conductor(s): helically wound tinned copper wires, approx. coverage 85 %
- 2 - 100 conductor(s): tinned copper braided shield, approx. coverage 85 %
-
- Outer jacket: PVC acc. to DIN VDE 0207-363-4-1 / DIN EN 50363-4-1 (compound type TM2)
-
- Jacket color: gray (RAL 7001)
-
- Length marking: in meters
Properties
-
- largely resistant to: oil,
- for details, see "Technical Information"
Tests
-
- flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
-
- certifications and approvals:
- 2 - 100 conductor(s): EAC
- 2 - 100 conductor(s): VDE Reg. No. 7034, valid for temperature range up to +70°C
Notes
-
- the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only
-
- please note "cleanroom qualification" in your order
Application
-
- For flexible use with free movement without tensile stress or forced movements in dry, moist and wet rooms but not outside; to be used as control and connecting cable in control and regulation technology, in the tool and machine building industry, in computer systems, as well as a signal cable in the electronic industry. A stabilizing foil separator between wire bound and braid reduces the outer diameter essentially and allows for smaller bending radius as well as lower weights. The disturbance free transmission of signals and impulses is ensured due to the high degree of screening. EMC = Electromagnetic Compatibility; in order to optimise EMC properties, we recommend a double-sided and all-round large contact area of the copper braiding.