H05RN-F black 4 G 0.75 mm² Part no. 36008
  • HAR certification
  • EAC certification
  • UKCA certification
  • Rubber connection cable
  • for light mechanical stress
  • for outdoor use

Item Details

Part no.
36008
Item description
H05RN-F black 4 G 0.75 mm²
AWG (approx.)
19
Outer Ø mm (approx.)
6.8 - 8.8
Cu factor per km
29.0
Weight kg/km (approx.)
94.0
Copper base in EUR / 100 kg
150
CPR class
Eca
Metres per Packaging Unit
100, 500, 1000
Cut-to-length service available
yes
EAN / GTIN
4060892168246
Customs tariff number
85444995

Technical Data

Rubber connection cable, H05RN-F acc. to DIN VDE 0285-525-2-21 / DIN EN 50525-2-21; 05RN-F in alignment with DIN VDE 0285-525-2-21 / DIN EN 50525-2-21
Temperature range flexible -25°C to +60°C
fixed -30°C to +60°C
Permissible operating temperature of the conductor +60°C
Nominal voltage AC U0/U 300/500 V
Max. permissible operating voltage alternating current (AC) conductor/earth 318 V
three-phase alternating current (AC) conductor/conductor 550 V
direct current (DC) conductor/earth 413 V
direct current (DC) conductor/conductor 825 V
Test voltage core/core 2000 V
Minimum bending radius 7.5x Outer-Ø

Details

Cable Structure

      • Copper wire bare, finely stranded acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
      • Core insulation: rubber acc. to DIN VDE 0207-363-1 / DIN EN 50363-1 (compound type EI4)
      • Core identification acc. to DIN VDE 0293-308, colour coded
      • Protective conductor: starting with 3 cores,
      • G = with protective conductor GN-YE,
      • x = without protective conductor
      • Cores stranded with optimal lay lengths
      • Outer sheath: rubber acc. to DIN VDE 0207-363-2-1 / DIN EN 50363-2-1 (compound type EM2)
      • Sheath colour: black

Properties

      • resistant to: weathering effects
      • for outdoor use

Tests

      • flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
      • certifications and approvals:
      • H05RN-F: HAR
      • H05RN-F: EAC

Notes

      • the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only

Application

      • Connection cable for use in dry, damp and wet rooms as well as outdoors; for connecting appliances in households, kitchens or offices involving light mechanical stress (e.g. hoovers, kitchen appliances and other portable household and garden equipment)
Info Circlechevron-leftAlertBrowse fileDownload fileFileImagePdfWordTextExcelPowerpointArchiveCsvAudioVideoSpinnerCalendarSort NoneSort ASCSort DESCReturn arrowMinusYouTubeSyncVisibleInvisible