NAY2Y noir 4 x 120 se mm² Numéro d'article 31179
  • Certificat VDE
  • Certificat UKCA

Détails de l'article

Numéro d'article
31179
Désignation de l'article
NAY2Y noir 4 x 120 se mm²
Ø extérieur mm (approx.)
42
indice Alu per km
1382,0
Poids kg/km (approx.)
2501,0
Base aluminium en EUR / 100kg
0
Mètre par unité de conditionnement
500, 1000
coupe individuelle possible
oui
EAN / GTIN
4060892266379
Numéro de tarif douanier
85444995

Caractéristiques techniques

Power distribution cables acc. to DIN VDE 0276-603 / HD 603 S1 / IEC 60502
Temperature range flexing -5°C to +50°C
fixed installation -40°C to +70°C
Permissible conductor operating temperature +70°C
Permissible short circuit temperature (short circuit duration max. 5 s) +160°C
Nominal voltage U0/U 600/1000 V
Test voltage 4000 V
Highest permissible voltage Direct current systems: Conductor/conductor 1.8 kV
Direct current systems: Conductor/earth 0.9 kV
Alternating current systems: Single phase systems both outer conductors insulated 1.4 kV
Alternating current systems: Single phase systems one outer conductor earthed 0.7 kV
Three phase systems 1.2 kV
Minimum bending radius 12x Outer-Ø

Détails du produit

Construction

      • Aluminium conductor,
      • single wire acc. to DIN VDE 0295 cl.1 / IEC 60228 cl.1
      • Core insulation: PVC
      • Core identification: GN-YE, BN, BK, GY
      • Cores stranded in concentric layers
      • Common core sheath
      • Outer sheath: PE
      • Sheath colour: black

Propriétés

      • the materials used during manufacturing are cadmium-free, contain no silicone and are free from substances harmful to the wetting properties of lacquers

Remarques

      • re = round conductor, single wire
      • se = sectional conductor, single wire
      • The conductor is metrically constructed (mm²). The AWG designation is approximate and purely informative.

Utilisation

      • Power cables for energy supply are installed in open air, in underground, in water, in concrete, indoors, in cable ducts, power stations, for industry and distribution boards as well as in subscriber networks. Usable in extreme working conditions due to the robust PE outer sheath.

Téléchargements

Info Circlechevron-leftAlertBrowse fileDownload fileFileImagePdfWordTextExcelPowerpointArchiveCsvAudioVideoSpinnerCalendarSort NoneSort ASCSort DESCReturn arrowMinusYouTubeSyncVisibleInvisible