TRAYCONTROL® 300-C grey 2 x 18 AWG
Part No. 62770
- Oil Res I/II
- exposed run: PLTC-ER, ITC-ER, CM, CMG, NFPA 79
- EMC-preferred type
Item Details TRAYCONTROL® 300-C grey 2 x 18 AWG
- Part No.
- 62770
- Item description
- TRAYCONTROL® 300-C grey 2 x 18 AWG
- Cross-sec. mm² (approx.)
- 0.96
- Outer Ø mm (approx.)
- 7.8
- Cu factor per km
- 43.0
- Weight kg/km (approx.)
- 100.0
- Copper base in EUR / 100 kg
- 150
- Metres per Packaging Unit
- 100, 500, 1000
- Cut-to-length service available
- yes
- EAN / GTIN
- 4060892095269
- Customs tariff number
- 85444995
Technical Data TRAYCONTROL® 300-C grey 2 x 18 AWG
PVC data cable acc. to UL-Std. 444 (CM), CSA-Std. C22.2 No. 214 - CMG, CSA-Std. C22.2 No. 210 - AWM I/II A/B, 28 AWG - 24 AWG: UL-Std. 758 (AWM) Style 2517, 22 AWG - 16 AWG: UL-Std. 758 (AWM) Style 2586, UL-Std. 2250 (ITC-ER), UL-Std. 13 (PLTC-ER) | |
Temperature range | flexible +5°C to +50°C fixed -25°C to +105°C |
Nominal voltage | AC U 300 V |
Test voltage core/core | 2000 V |
Test voltage core/screen | 2000 V |
Minimum bending radius | flexible 12x Outer-Ø fixed 6x Outer-Ø |
Details TRAYCONTROL® 300-C grey 2 x 18 AWG
Cable Structure
-
- Copper wire tinned, finely stranded acc. to ASTM B174 Class K, AWG sizes
-
- Core insulation: see datasheet
-
- Core identification acc. to company specifications, colour coded
-
- Cores stranded in layers with optimal lay lengths
-
- Drain wire
-
- 1. Screen: plastic-coated aluminium foil (St)
- 2. Screen: braided screen of tinned copper wires, approx. coverage 85%
-
- Separator
-
- Outer sheath: Special-PVC
-
- Sheath colour: grey (RAL 7001)
-
- Length marking: in feet
Properties
-
- resistant to: oil
-
- for outdoor use
-
- the materials used during manufacturing are cadmium-free, contain no silicone and are free from substances harmful to the wetting properties of lacquers
Tests
-
- flame-retardant acc. to CSA FT4
-
- oil-resistant acc. to UL Std 1277 Tab. 12.2, Oil Res I / Oil Res II
-
- Cold Bend Test acc. to UL Std. 1277 No. 17
-
- Impact Test (-ER) acc. to UL Std. 1277 No. 23
-
- Crushing Test (-ER) acc. to UL Std. 1277 No. 24
-
- Vertical-Tray Flame Test (FT4) CSA-Std. C22.2 No. 2256
-
- certifications and approvals:
- EAC
- ECOLAB®
Notes
-
- Conductor sizes are based on the AWG measurement system, metric conductor sizes (mm²) are approximated and are for reference only
Application
-
- TRAYCONTROL® 300-C is a flexible PVC data cable. The special combination of PLTC-ER and ITC-ER allows this cable to be used as a connecting cable for industrial plant and machinery in accordance with NFPA 79. Approved for open, unprotected installation in cable trays to the machine. The double-shielding with aluminum foil (100% coverage) and copper braid (approx. 85% coverage) guarantee superior EMC protection. Recommended applications: machine tools, control panels, control and instrumentation technology, production automation, cable ducts, and renewable energy. 22 – 16 AWG: resistant to UV radiation (SUN RES); 18 – 16 AWG: direct burial (DIR BUR).